Cross-sections, current-carrying capacity, voltage drop and protection

Which electrical checks the app runs on power cables: current-carrying capacity in a bundle, voltage drop from the power connection, fault loop, protective device matching and leakage behind an RCD.

4 min read
Documentation contents ▾

After power is planned, the app checks every power cable. The checks use the lengths from the routes, so results change when you move a distribution board or loads. Every warning gives the numbers and proposes a fix.

Voltage drop

The drop is calculated in cascade: from the power connection through the cable to the main distribution board, the sub-distribution board and the circuit, down to the last load in the chain. Single-phase circuits: ΔU = 2 · L · I · ρ / S relative to 230 V. Three-phase cables to distribution boards: using the current of the most heavily loaded phase and the neutral conductor current (with balanced phases this equals √3 · L · I · ρ / S relative to 400 V). Assumed copper resistivity ρ = 0.0225 Ω·mm²/m.

ThresholdDefault (mains)With a generator
Warning3 %6 %
Error5 %8 %

You change the thresholds in the wizard: Rules → Voltage drop: warning (1–10 %) and Voltage drop: error (1–15 %). The error threshold must be higher than the warning threshold, otherwise the wizard will not let you plan.

The warning tells you where the drop occurs, e.g. "voltage drop to the last load 6.1 % (including distribution board feed 2.3 %)". It lists up to three circuits of one distribution board separately, and more than that as a group.

Voltage drop fixes

  • Change cross-section: a larger cross-section in the same connector system, e.g. Schuko 3G1.5 → 3G2.5, CEE 32 A 5G6 → 5G10. The fix is only proposed when, after picking the standard length, the cable resistance drops by at least 10 %.
  • Split circuit: lower current in the chain, when the circuit has at least two loads.
  • Move distribution board: the planner's distribution board moves closer to the loads.

Current-carrying capacity of conductors

For H07RN-F rubber cables, the app assumes the current-carrying capacity in free air at 30 °C and corrects it with three factors:

Ambient temperature
30 °C indoors, 35 °C outdoors (project environment). Above 30 °C capacity drops, down to 0.58 at 50 °C.
Bundle
Number of circuits running together on the floor over at least 1 m. The factor drops from 0.8 for two circuits to 0.38 for 20 or more. Lightly loaded cables are not counted in the bundle.
Multipin
A cable with more than three loaded cores gets an additional factor.

A load current above the corrected current-carrying capacity is an error. A protective device rated above the capacity is a warning: the cable is then not protected against overload. Fixes: Change cross-section or Separate cables (route next to the bundle instead of inside it).

Protection and fault loop

The protection check verifies that the protective device current at the start of the cable does not exceed its current-carrying capacity or the input current of the distribution board it feeds. Example: a 63 A distribution board fed directly from a Powerlock 400 A gets an error, and the fix Replace distribution board or Recalculate power places a main distribution board at the power connection with outgoing feeds that have the correct protection.

L-N fault loop: source impedance + 2 × the sum of cable resistances from the power connection to the furthest load must not exceed 230 V / Ia. Ia is the trip current of the breaker: 5 × In for curve B, 10 × In for C, 20 × In for D. Assumed source impedance: 0.3 Ω for mains and 0.6 Ω for a generator.

RCD and leakage current

For circuits with a 30 mA RCD, the app sums the estimated protective conductor leakage current: 1.5 mA per LED cabinet and 1.0 mA per fixture. The recommended total is up to 30 % of the residual current rating, i.e. 9 mA for a 30 mA RCD. Exceeding it gives a warning with the Split circuit fix, and for a screen a note to check the leakage current in the cabinet datasheet and split the screen across more RCDs.

Cables with manual settings

If a warning concerns a locked cable, one with a manual length or a manually chosen type, the warning text says so directly: the planner does not change such a cable, the decision is yours.

Did not find the answer?
Describe the problem and we will reply with a solution or add an article.